Appendix

Drawings gallery · P&ID · psychrometric chart · mass balance · sensitivity · calculations · glossary

Drawings gallery — fabrication drawings

S1 — Plan
S1 — Plan
S2 — Longitudinal section (supply channel)
S2 — Longitudinal section (supply channel)
S3 — Cross-section
S3 — Cross-section
S4 — Elevations
S4 — Elevations
S5 — Air circuit & specs
S5 — Air circuit & specs
S6 — Trolley fabrication
S6 — Trolley fabrication

Drawings gallery — process & control diagrams

S7 — P&ID: refrigerant + air + condensate
S7 — P&ID: refrigerant + air + condensate
S8 — Psychrometric chart with state points
S8 — Psychrometric chart with state points
S9 — Site plan & service interfaces
S9 — Site plan & service interfaces
S10 — Control state diagram
S10 — Control state diagram

3D renders

3D cutaway.
3D cutaway.
Trolley inspector (exploded).
Trolley inspector (exploded).
CFD velocity.
CFD velocity.
CFD relative pressure.
CFD relative pressure.
Velocity vector field.
Velocity vector field.

Validation results

The thermodynamic model in the source tool is cross-checked against an independent Python implementation at every commit. For the target configuration, all 20 compared values match to 3 decimal places (relative error < 1%):

QuantityToolReferenceStatus
Tray area181.9 m²181.9OK
Fresh batch1,819 kg1,819OK
Drying time19.7 h19.7OK
Airflow10,653 m³/h10,653OK
HP required85.9 kW85.9OK
SMER4.034.03OK
Pressure budget410 Pa410OK

…13 more values all match. Sanity ranges pass: drying 10–20 h, SMER 2.5–4.5 kg/kWh, coil > 5°C (no frost), return RH < 90%.

Mass & energy balance (per batch)

FlowInOutNotes
Fresh coconut (50% MC)1,819 kgLoaded on trays
Water removed862 kgCondensed at evaporator, drained
Copra out (5.0% MC)957 kgUnloaded after cycle
Solids (dry matter, conserved)910 kg895 kgCheck: solids in = solids out ✓
Energy flowkWh/batchNotes
Latent heat (water evaporated)~570Recovered at evaporator, reused at condenser
Structure heat loss (walls)~25Lost to ambient through PUF panels
Product heat-up~4130°C → 62°C, transient (first 1.5 h)
Fan motor heat~34Enters air stream (offsets condenser)
Total electricity consumed214= (thermal / COP) + fan

Sensitivity analysis

How robust is the design to variation in key inputs? Each row changes one parameter by ±15–20% from the design point and reports the impact.

ParameterLowDesignHighImpact
Loading (kg/m²)81012 Batch ±20%; SMER stable 3.4–3.7; drying time unchanged (ratio-based)
Supply temp (°C)576265 Drying time 24 h → 19.7 h → 16 h; case-hardening risk rises above 65°C
Face velocity (m/s)2.42.83.2 Return RH 85→71→60%; fan power +44%; ΔP rises proportionally
Ambient temp (°C)253035 Wall loss ±0.4 kW (negligible); HP sizing unaffected
HP COP2.83.23.6 SMER 3.2→3.6→4.0; electricity per batch ±12%

All sensitivities computed within the tool by adjusting the relevant parameter and re-running the thermo engine. Design point is highlighted; the system remains feasible (no warnings) across the full range shown.

Worked calculations summary

HP sizing (how 86 kW is derived)

peak_rate = water / t_dry × peak_factor = 862 / 19.7 × 1.3 = 56.8 kg/h
peak_latent = peak_rate × h_fg / 3600 = 56.8 × 2381 / 3600 = 38 kW
required = (peak_latent + loss + product_heatup) × 1.15
    = (38 + 1.7 + 28.7) × 1.15 = 86 kW
installed = 2 × 50 kW modules (staged)

Wall U-value

U = 1 / (R_inside + R_PUF + R_outside)
  = 1 / (0.13 + 0.050/0.022 + 0.04)
  = 1 / 2.44 = 0.41 W/m²·K
loss = U × A_env × ΔT / 1000 = 0.41 × 92.8 × 32 / 1000 = 1.2 kW

Fan affinity law (why velocity matters)

Q ∝ N (flow ∝ speed)
ΔP ∝ N² (pressure ∝ speed²)
Power ∝ N³ (power ∝ speed³)
→ A 15% velocity increase costs 52% more fan power.

Psychrometric formulas

p_ws(T) = 0.61094 · exp(17.625·T / (T + 243.04)) kPa  [Magnus, water]
W(T, RH) = 0.62198 · p_w / (P − p_w)  where p_w = RH · p_ws(T)
h(T, W) = 1.006·T + W·(2501 + 1.86·T)  kJ/kgda
v_da(T, W) = 287.055 · (T + 273.15) / ((P − p_w) · 1000)  m³/kgda
T_dp(W) = inverse Magnus on p_w = W·P / (0.62198 + W)

Glossary

SMERSpecific Moisture Extraction Rate — kg of water removed per kWh of electricity consumed
COPCoefficient of Performance — heat delivered / electrical input (heat-pump basis)
W (humidity ratio)kg of water vapour per kg of dry air
Page modelThin-layer drying equation MR = exp(−k·tn)
PUFPolyurethane Foam (insulation); 50 mm sandwich panel
U-flowAir path: supply down one channel, U-turn at door end, return via parallel channel
CircuitOne 1-U-turn air path (this design: 1 circuit, 2 channels)
AbreastTrolleys side-by-side within a channel sharing the same airflow
← 11 · VendorPage 12 of 12