Heat-Pump Specification

Staged capacity · refrigerant · coils · compressor · condensate

Capacity & staging

Required heating capacity (peak, with 15% margin)86 kW
Compressor electrical input (COP 3.2)27 kW · ~36 HP motor
Peak latent load37.6 kW
Average batch load~24 kW (HP will modulate)
Recommended arrangement2 × 50 kW modules in parallel (staged, redundant)
Alternative3 × 30 kW modules (finer staging, higher redundancy)

Why staged modules, not one big unit

The batch moisture load peaks early and falls to ~50% by mid-cycle. A single 86 kW unit would short-cycle for the second half of the batch. Two 50 kW modules let you run both during the peak and drop to one as the load falls — better part-load efficiency and full redundancy (one module down = half capacity, not a stoppage). Standard 50 kW heat-pump units are easier to source than a custom 120 kW unit.

Refrigerant & coils

ItemSpecification
RefrigerantR410A (acceptable) or R32 / R454B (low-GWP, recommended for new builds)
Evaporator coilFin-and-tube, 4-row, ~95 kW design duty, face area sized for <2.5 m/s face velocity
Condenser coilFin-and-tube, 4-row, ~88 kW design duty, reheat the mixed stream to 62°C
Condensate drain32 mm SS, U-trap (50 mm seal), routed to a 200 L holding tank for batch metering
DefrostHot-gas reverse-cycle; coil outlet ≥ 5°C at design point — defrost rare (governed by sensors)
CompressorScroll or screw, semi-hermetic, capacity control 25–100%, IE3 motor

State diagram

The psychrometric chart (S8) below shows the three air states on a temperature–humidity plot, with the process path: supply (3) → through product picking up moisture (1) → through evaporator condensing water (2) → reheated by condenser back to (3). The closed loop is clearly visible.

S8 — Psychrometric chart with state points 1, 2, 3 and the process path through product, evaporator, and condenser.
S8 — Psychrometric chart with state points 1, 2, 3 and the process path through product, evaporator, and condenser.
StageStateT (°C)RH (%)W (kg/kg)
Supply (post-condenser)362.0200.0282
Return from product136.6980.0380
Off evaporator (sat)216.2100

Vendor schedule (HP scope)

The P&ID below (S7) shows the complete piping, instrumentation, and air loop for one HP module plus the room. Vendors should confirm all instrument tags and pipe sizes against this diagram.

S7 — Piping & Instrumentation Diagram: refrigerant loop (orange), air loop (white), condensate (dashed), with instrument tags.
S7 — Piping & Instrumentation Diagram: refrigerant loop (orange), air loop (white), condensate (dashed), with instrument tags.
ItemQtySpec
Heat-pump dehumidifier module2 50 kW heating, COP ≥ 3.2 at 62°C cond / 20°C evap, R410A or R32
Evaporator condensate assembly2Per module, with U-trap and tank takeoff
Control panel per module2PLC with capacity control, Modbus RTU to master BMS
Refrigerant pressure / leak sensors2 setsHard interlock to fans and alarm beacon
Vibration isolators, refrigerant piping to module boundaryPer module

Condensate management

~862 kg (litres) of water per batch is removed at the evaporator and drained as liquid. This is not vented — it is collected in a 200 L calibrated tank and measured each batch as a process check (sum of condensate + final moisture check = batch mass balance).

← 5 · AirflowPage 6 of 127 · Controls →